Place of Origin: | China |
---|---|
Brand Name: | XWH |
Certification: | CE, ISO |
Model Number: | XW-2HP, XW-3HP, XW-5HP |
Minimum Order Quantity: | 1 |
Price: | USD1300-USD2000 |
Packaging Details: | Wooden Case |
Delivery Time: | 15 working days |
Payment Terms: | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Supply Ability: | 500 sets/month |
Product Name: | Industrial Water Chiller | Application: | Industriy |
---|---|---|---|
MOQ: | 1 Set | Cooling Type: | Air Cooled Condenser Chiller |
Production Time: | 15-20 Days | Usage: | Injection Molding Cooling Machine |
After Warranty Service: | Video Technical Support, Online Support And Spare Parts | After-sales Service Provided: | Free Spare Parts, Field Installation, Commissioning And Training |
High Light: | Cw3000 Industrial Water Chiller,1Hp Industrial Water Chiller,Air Cooled Water Chiller Cw 5200 |
Cw3000 Cheap Cw 5000 Cw 5200 1 Hp Industrial Cw 5200 Air Cooled Water Chiller
Product Description
Industrial water chiller is mainly suitable for plastic and mechanical processing. It can accurately control the temperature of plastic’s forming mold to shorten the molding cycle and speed up the product shaping; this series uses the principle of cold and heat exchange for cooling, which can be cooled quickly and the temperature control is stable. And not affected by environmental factors, it is an indispensable configuration equipment in modern industry.
Technical Parameters
Item/Model | XW-2HP | XW-3HP | XW-5HP |
Total Power | 1.9KW | 2.625KW | 4.485KW |
Input Voltage | 220V/3PH/60Hz | 380V/3PH/50HZ | 380V/5PH/50HZ |
Cooling Capacity | 4128KCAL/HR/4.8KW | 7713KCAL/HR/9KW | 12900KCAL/HR/15KW |
cooling Fans Number | 1 set | 2 sets | 2 sets |
Tank Capacity | 35L | 67L | 60L |
Pump Flow Rate | 100L(min) | 100L(min) | 50L/min |
Temperature Control Range | 5℃-35℃ | 5℃-35℃ | 5℃-35℃ |
Refrigerant | R22 | R22 | R22 |
Weight | 120KG | 140KG | 160KG |
Dimension | 850*520*1020mm | 1230*500*1120mm | 1400*570*1220mm |
Features
1. High efficiency foil aluminum fin condenser.
2. Tank coil evaporator (copper tube).
3. Using Stainless steel water tank.
4. Complete protection functions (phase loss, reverse phase, over temperature, high and low pressure, overload).
5. Using high quality computer board, the temperature is accurate to ±1℃.
6. Using Germany Schneider AC contactor and phase sequence relay.
7. Using ALCO filters.
8. Using American YK306F pressure controller.
Is the High and Low Pressure Normal?
When the water-cooled compressor is in normal operation, the high pressure display of 12~15kg/cm2 is the best, (the air-cooled 13~17kg/cm2 is the best) but not higher than 20kg/cm2, when the water-cooled pressure is higher than 20kg /cm2, or the air-cooled pressure is higher than 24kg/cm2, please refer to Note (1) for high-pressure switch tripping. For low pressure, 2.5~4.5kg/cm2 is the best, but not less than 2kg/cm2. For 2kg/cm2 low pressure trip, please refer to Note (2) for handling.
When the difference between the high pressure and the low pressure is very small or equal based on the running state of the compressor, it means that the valve of the compressor is damaged or broken. Please stop the operation immediately and notify the distributor or manufacturer.
Installation Diagram of Air-cooled Chiller
Frequently Asked Questions